IEVref:351-45-17ID:
Language:enStatus: Standard
Term: reset windup
Synonym1: integral windup
[Preferred]
Synonym2:
Synonym3:
Symbol:
Definition: phenomenon in a system, where an integral element is followed by a non-linear element operating within its saturation range, resulting in the delay of response of the output variable to a change of sign of the input variable

Note 1 to entry: In a control loop this delay of response of the output variable may cause excessive overshooting of the controlled variable.

Note 2 to entry: This entry was numbered 351-24-16 in IEC 60050-351:2006.


Publication date:2013-11
Source
Replaces:
Internal notes:
CO remarks:
TC/SC remarks:
VT remarks:
Domain1:
Domain2:
Domain3: